• 4KVA – 24V Inverter – H

    nverter Output
    Model PT-INV-4KVA 24V-Color LED, Wall-H
    Continuous Output Power 3000W
    Surge Rating(20s) 9000W
    Capable of Starting Electric Motor 3HP
    Output Waveform Pure Sine wave/Same as input(Bypass mode)
    Nominal Efficiency >88%(Peak)
    Line Mode Efficiency >95%
    Power Factor 0.9-1.0
    Nominal Output Voltage rms 100-110-120Vac / 220-230-240Vac
    Output Voltage Regulation ±10% RMS
    Output Frequency 50/60Hz ± 0.3Hz
    Short Circuit Protection Yes, Current Limit Function (Fault after 1sec)
    Typical transfer Time 10ms(Max)
    THD < 10%
    DC Input
    Nominal Input Voltage 12.0Vdc
    ( *2 for 24Vdc, *4 for 48Vdc)
    Minimum Start Voltage 10.0Vdc
    Low Battery Alarm 10.5Vdc / 11.0Vdc
    Low Battery Trip 10.0Vdc / 10.5Vdc
    High Voltage Alarm & Fault 16.0Vdc
    High DC Input Recovery 15.5Vdc
    Low Battery voltage recover 13.0Vdc
    Idle Consumption-Search Mode < 25 W when Power Saver On
    Charge
    Input Voltage Range Wide: 90~135VAC / 164~243VAC
    Narraw: 100~135VAC / 194~243VAC
    Input Frequency Range Narrow: 47-55±0.3Hz for 50Hz, 57-65±0.3Hz for 60Hz
    Wide:43±0.3Hz plus for 50Hz/60Hz
    Output Voltage Depends on battery type
    Charger Breaker Rating 30A
    Max Charge Rate 30 ± 5A
    Over Charge Protection Shutdown 15.7V for 12Vdc ( *2 for 24Vdc, *4 for 48Vdc)
    Charger curve(4 stage constant current)
    4 step digital controlled progressive charge
    Battery types ( *2 for 24Vdc, *4 for 48Vdc)
    Battery type Fast Vdc
    Gel U.S.A 14.0
    A.G.M 1 14.1
    A.G.M 2 14.6
    Sealed Lead Acid 14.4
    Gel Euro 14.4
    Open Lead Acid 14.8
    Calcium 15.1
    De-sulphation 15.5 for 4hrs
    Remote Control Yes. Optional
    Bypass & Protection
    Input Voltage Waveform Sine wave (Grid or Generator)
    Nominal Voltage 120Vac
    Low Voltage Trip 80V/90V±4%
    Low Voltage re engage 90V/100V±4%
    High Voltage Trip 140V±4%
    High Voltage re engage 135V±4%
    Max Input AC Voltage 150VAC
    Nominal Input Frequency 50Hz or 60Hz (Auto detect)
    Low Freq Trip Narrow: 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz
    Wide:40±0.3Hz for 50Hz/60Hz
    Low Freq re engage Narrow: 48±0.3Hz for 50Hz, 58±0.3Hz for 60Hz
    Wide:42±0.3Hz for 50Hz/60Hz
    High Freq Trip Narrow: 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz
    Wide: 70±0.3Hz for 50Hz/60Hz
    High Freq re engage Narrow: 54±0.3Hz for 50Hz, 64±0.3Hz for 60Hz
    Wide: 68±0.3Hz for 50Hz/60Hz
    Output Short circuit protection Circuit breaker
    Bypass breaker rating 30A
    Transfer switch rating 40amp for UL
    Max bypass current 40amp
    Mechanical Specification
    Mounting Wall mount
    Inverter Dimensions(L*W*H) 670*350*300mm
    Inverter Weight 17KG
    Shipping Dimensions(L*W*H) 585x320x310mm
    Shipping Weight 20KG
    Display Status LEDs / Status LEDs+LCD
    Standard Warranty 1 Year

     