Input |
Voltage |
230 Vac |
Tolerance |
Normal Over-voltage: +10% |
|
Withstand Over-voltage: +15% (20% max limit) |
|
Normal Under-voltage: – 20% |
|
Withstand Low-voltage: – 30% (-37% lowest limit) |
Power Factor |
0.98 |
|
|
Output |
|
Voltage |
230Vac ± 1% |
Power Factor |
FS-R Model: 0.8 |
|
FS-R-V Model: 0.9 |
Transfer Time |
0 ms |
Frequency |
46 – 54Hz (On Mains) |
|
50Hz (On Battery) |
Waveform |
Pure Sine Wave |
THDi |
Linear Load ≤ 3%; Non-linear Load ≤ 6% |
Crest Factor |
3 : 1 |
Bypass Facility |
Static Bypass |
|
|
DC Bus / DC Functions: |
1kVA |
36V |
2kVA |
72/96V |
3kVA |
96V |
6/10kVA |
192V |
Cold-Start Function |
Yes |
Charging Time |
6hr to recover to 90% capacity |
Battery Charging in OFF Mode |
Yes |
Battery Type |
Sealed, Maintenance-free VRLA |
|
|
LCD User Interface: |
|
Metering / Indications for |
Voltage |
|
Load % |
|
Frequency |
|
General Status |
|
Alarm |
|
|
Communication: |
|
Interfaces |
RS232, USB*, SNMP* (* Option) |
|
|
Overload |
|
100~110% |
Output swithes to bypass after 60s |
125~130% |
Output swithes to bypass after 30s |
>130% |
Output swithes to bypass after 100ms |
|
|
Environment: |
|
Temperature |
0 ~ 40oC |
Humidity |
20 ~ 90% Non-condensing |
Noise Level |
< 50dB from 1m |
IP Class |
IP 20 |
|
|
Physical: |
|
Dimensions (mm) |
1-3kVA : 480 x 485 x 88, 2U (W x D x H) |
|
6-10kVA : 480 x 600 x 220, 5U (W x D x H) |
|
|
Weight (Kg) |
1kVA : 13kg |
UPS with 1 battery pack |
2kVA : 31kg |
|
3kVA : 32kg |
|
6kVA : 85kg |
|
10kVA : 87kg |
Reviews