“SRN 3KW, 24V Hybrid inverter” was added to the compare list
Roll over image to zoom in
Click to open expanded view
DEYE 12kW Hybrid Inverter
In stock
PRODUCT SPECIFICATIONS
Model
SUN-12K-SG01LP1-EU
SUN-14K-SG01LP1-EU
SUN-16K-SG01LP1-EU
Battery Input Data
Battery Type
Lead-acid or Lithium-ion
Battery Voltage Range (V)
40-60
Max. Charging Current (A)
220
250
290
Max. Discharging Current (A)
220
250
290
Charging Strategy for Li-ion Battery
Self-adaption to BMS
Number of Battery Input
2
PV String Input Data
Max. PV Access Power (W)
24000
28000
32000
Max. PV Input Power (W)
19200
22400
25600
Max. PV Input Voltage (V)
500
Start-up Voltage (V)
125
MPPT Voltage Range (V)
150-425
Rated PV Input Voltage (V)
370
Max. Operating PV Input Current (A)
26+26+26
26+26+26
26+26+26
Max. Input Short-Circuit Current (A)
44+44+44
44+44+44
44+44+44
AC Input/Output Data
Rated AC Input/Output Active Power (W)
12000
14000
16000
Max. AC Input/Output Apparent Power (VA)
13200
15400
17600
Rated AC Input/Output Current (A)
54.5/52.2
63.6/60.9
72.7/69.6
Max. AC Input/Output Current (A)
60/57.4
70/67
80/76.5
Max. Continuous AC Passthrough (grid to load) (A)
100
100
100
Peak Power (grid to load) (W)
2 times of rated power, 10s
Power Factor Adjustment Range
0.8 leading to 0.8 lagging
Rated Input/Output Voltage Range (V)
220/230, 0.85Un-1.1Un
Rated Input/Output Grid Frequency/Range(Hz)
50/45-55, 60/55-65
Grid Connection Form
L-N-PE
Total Current Harmonic Distortion THDi
<3% (of nominal power)
DC Injection Current
<0.5% In
Equipment Protection
Integrated
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Detection and Protection, Output Residual Current Detection, Switch Insulation Impedance Detection, DC Disconnect, Circuit Breaker
Reviews