Specification |
Model NB |
12396/192 |
153192/240 |
203192/240 |
253240 |
Rated Power |
12KW |
15KW |
20KW |
25KW |
Peak Power(20ms) |
36KW |
45KW |
60KW |
75KW |
Start Motor |
7HP |
10HP |
10HP |
15HP |
Battery Voltage |
96/192VDC |
192/240VDC |
192/240VDC |
240VDC |
Size(L*W*Hmm) |
600*300*800 |
Packing Size(L*W*Hmm) |
665*365*830 |
N.W.(kg) |
102 |
108 |
113 |
119 |
G.W.(kg)(Carton Packing) |
115 |
121 |
130 |
136 |
Installation Method |
Tower |
Parameter |
Input |
DC Input Voltage Range |
10.5-15VDC(Single battery voltage) |
AC Input Voltage Range |
98VAC~125VAC / 195VAC~250VAC |
AC Input Frequency Range |
45Hz~64Hz |
Max AC charging current |
6A~15A (Depending on the model) |
AC charging voltage |
LEAD battery:Charge Voltage :14V; Float Voltage:13.8V(Single battery voltage) |
AC charging method |
Three-stage (constant current, constant voltage, floating charge) |
Output |
Efficiency(Battery Mode) |
≥85% |
Output Voltage(Battery Mode) |
110VAC±2% / 220VAC±2%(Battery Mode) |
Output Frequency(Battery Mode) |
50Hz±0.5 or 60Hz±0.5 |
Output Wave(Battery Mode) |
Pure Sine Wave |
Efficiency(AC Mode) |
>99% |
Output Voltage(AC Mode) |
110VAC±10% / 220VAC±10% |
Output Frequency(AC Mode) |
Tracking Automatically |
Output waveform distortion(Battery Mode) |
≤3%(Linear load) |
No load loss(Battery Mode) |
≤1% rated power |
No load loss(AC Mode) |
≤2% rated power( charger does not work in AC mode) |
No load loss(Energy saving Mode) |
≤10W |
Battery Type |
Customize battery |
Charge and discharge parameters of different types of batteries (such as lithium batteries, etc.)
can be customized according to user requirements |
Protection |
Battery undervoltage alarm |
11V(Single battery voltage) |
Battery undervoltage protection |
10.5V(Single battery voltage) |
Battery overvoltage alarm |
15V(Single battery voltage) |
Battery overvoltage protection |
17V(Single battery voltage) |
Battery overvoltage recovery voltage |
14.5V(Single battery voltage) |
Overload power protection |
Automatic protection (battery mode), circuit breaker or insurance (AC mode) |
Output short circuit protection |
Automatic protection (battery mode), circuit breaker or insurance (AC mode) |
Temperature protection |
>90°C(Shut down output) |
Alarm |
A |
Normal working condition, buzzer has no alarm sound |
B |
Buzzer sounds 4 times per second when battery failure, voltage abnormality, overload protection |
C |
When the machine is turned on for the first time, the buzzer will prompt 5 when the machine is normal |
Working Mode |
Battery First/AC First |
Transfer Time |
≤4ms |
Display |
LCD |
Thermal method |
Cooling fan in intelligent control |
Communication |
RS232(Optional) |
Environment |
Operating temperature |
-10℃~40℃ |
Storage temperature |
-15℃~60℃ |
Noise |
≤55dB |
Elevation |
2000m(More than derating) |
Humidity |
0%~95% ,No condensation |
Warranty |
1 year |
Note: All specifications are subject to change without prior notice |